Tests Of The Woolley Valve For The James H. Campbell Plant, Unit No. 3
Alternative title
Published Date
1979-11
Publisher
St. Anthony Falls Laboratory
Type
Report
Abstract
The innovative use of fixed screens to reject solids in condenser
cooling water drawn from Lake Michigan has been considered a practical
solution for the lake withdrawal system proposed at the James H. Campbell,
Unit No.3 Of the Consumer Power Company. The withdrawal point, which is
3,500 feet offshore and approximately 30 feet below the lake surface, is
considered relatively free of screen-plugging.solids under normal conditions,
but during winter, frazil ice plugging is possible. To assure continued
operation under these unusual conditions it was considered necessary to
provide the system with an opened water (non-screened) auxiliary intake.
This auxiliary function is to be provided by installing a relief valve at
the outer or stub end of two of the four header pipes which are to constitu.te
the intake system as shown in Fig. 1. These valves are to open and provide
.auxiliary intake water whenever screen plugging resulted in a selected level
of pressure reduction within the header. The selected level proposed for
the valve operation was 12 inches additional headloss. The valve deemed
most appropriate for use was a modified version of a Synchro-chek valve made
by the W. J. Woolley Company of River Forest, Illinois.
The Woolley valve has been marketed for many years as a pump discharge
check valve, but its performance under Wave conditions, including 100 year
storms, at the proposed site were unknown. In order to clarify the valve
.performance it was decided to conduct tests of a 1:4 scale-model valve at
the St. Anthony Falls Hydraulic Laboratory of the University of Minnesota.
The material which follows describes the Woolley valve, the three part test
program (static, steady state flow, and dynamic flow), the test facilities,
the test results, and the conclusions and recommendations resulting from
the tests.
Keywords
Description
Related to
Replaces
License
Collections
Series/Report Number
St. Anthony Falls Laboratory Project Reports
181
181
Funding information
Consumer Power Company; Commonwealth Associates
Inc
Isbn identifier
Doi identifier
Previously Published Citation
Other identifiers
Suggested citation
Ripken, John F.; Dahlin, Warren Q.; Wood, Addison O.; Ferguson, Jeffrey E.. (1979). Tests Of The Woolley Valve For The James H. Campbell Plant, Unit No. 3. Retrieved from the University Digital Conservancy, https://hdl.handle.net/11299/118562.
Content distributed via the University Digital Conservancy may be subject to additional license and use restrictions applied by the depositor. By using these files, users agree to the Terms of Use. Materials in the UDC may contain content that is disturbing and/or harmful. For more information, please see our statement on harmful content in digital repositories.